E6582175
M-5
[Trip information]
Error code
Failure code
Name
Description
Remedies
0034
Over torque boost
fault
The automatic torque boost parameter
setting is too high.
The motor has too small impedance.
Set a lower automatic torque boost
parameter
setting.
Make an auto-tuning.
0035
CPU fault 2
The control CPU is defective.
Contact your Toshiba distributor.
0037
Optional unit fault 2
An optional device is defective.
Contact your Toshiba distributor.
003A
CPU fault 3
The control CPU detected a fault.
Reset the inverter. The cause can be
surrounding noise. If the problem is not
solved, contact your Toshiba distributor.
0063
Heavy cycle of main
power ON/OFF
Main power ON/OFF during running is
repeated frequently.
Initial failure if it is caused by other
reasons.
Reduce the frequency of repetition of
main power ON/OFF during running.
Contact your Toshiba distributor.
0040
PTC fault
PTC thermal protection is occurred.
Check the PTC in motor.
0045
Servo lock fault
The motor shaft is not locked in servo lock
operation.
Reduce the load in servo lock operation.
0047
Auto-tuning error
(PM motor)
When auto-tuning (relating parameters
are
pt
=
6
,
f400
=
2
), the current of
the permanent magnet motor exceeded
the threshold level.
The inductance of permanent magnet
motor is too small.
Auto tuning for permanent magnet motor
is not allowed for this motor, please
measure inductance with the LCR meter
etc.
The motor is not connected.
Set V/F control mode selection
pt
=
0
,
for operation check without connecting
motor.
* This marking trips can be selected valid or invalid by parameters.