E6582175
F-117
6
6.29.17 Number of starting alarm
f648
:
Number of starting alarm
Function
Counting the number of starting, when it will reach the value of parameter
f648
setting, it will be
displayed and alarm signal is output.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f648
Number of starting alarm
0.0-999.0 (10000 times)
999.0
● “0.1” displayed on the monitor refers to 1000 times, and therefore "1.0" denotes 10000 times.
Ex.: 38.5 displayed on the monitor = 385000 (times)
● Display of number of starting alarm information
Number of starting alarm information in the Status monitor mode allows you to check on the time of
replacement. (Refer to chapter 8)
An example of display:
● Output of number of starting alarm signal
The number of starting alarm is assigned to the output terminal.
Setup example) When the number of starting alarm is assigned to the OUT terminal
Title
Function
Adjustment range
Setting
f131
Output terminal selection 2A (OUT) 0-255
162: NSA (Number of
starting alarm)
Setting value 163 is reverse signal.
● The number of starting, forward number of starting and reverse number of starting until present time can be
monitored by setting status monitor mode. (Refer to chapter 8)
● The monitor value of the number of starting, number of forward run and number of reverse run are reset to
0 (zero) by setting
typ
=
12
(number of starting clear). (Refer to section 4.3.2)