Note: This function is valid when doing forward/reverse switching.
When starting operation,
f256
function will not work until output frequency reaches
ll
.
When the output frequency exceeds
ll
,
f259
function will be invalid until operation signal is OFF.
6.14 Jog run mode
f260
: Jog run frequency
f261
: Jog run stopping pattern
f262
: Panel jog run mode
Function
Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal immediately
generates a jog run frequency output irrespective of the designated acceleration time.
Also, you can choose the jog run start/stop mode from the panel.
Assign 18: jog run mode to an input terminal.
Ex) When assigning it to the RES terminal:
f113
to
18
.
The motor can be operated in jog mode while the assigned input terminals are connected (RES-CC ON).
[Parameter setting]
Title
Function
Adjustment range
Default setting
f260
Jog run frequency
f240
-20.0 (Hz)
5.0
f261
Jog run stopping
pattern
0: Deceleration stop
1: Coast stop
2: DC braking
0
f262
Panel jug run mode
0: Invalid
1: Valid
0
Output frequency [Hz]
Time[
s
]
ON
OFF
ll
+
f391
ll
Forward/ reverse