[Trip information]
Error code
Failure code
Name
Description
Remedies
0001
Overcurrent during
acceleration
The acceleration time
is too short.
Increase the acceleration time
.
The V/F setting is improper.
Check the V/F parameter setting.
A restart signal is input to the rotating
motor after a momentary stop, etc.
Use
(auto-restart) and
(ride-through control).
A special motor (e.g. motor with a small
impedance) is used.
In case of
pt
=
0
,
1
,
7
, decrease
vb
.
In case of
pt
=
2
to
6
, set
f415
(Motor rated current) and make an auto-
tuning.
Low inductance motor especially High
speed motor is used.
Choose the higher power range drive.
(1 class up drive is recommended.)
The connecting cable length with a motor
is long.
AC reactors etc. are required for the
output side. (Refer to section 1.4.3-(4).)
0002
Overcurrent during
deceleration
The deceleration time
is too short.
Increase the deceleration time
.
Low inductance motor especially High
speed motor is used.
Choose the higher power range drive.
(1 class up drive is recommended.)
The connecting cable length with a motor
is long.
AC reactors etc. are required for the
output side. (Refer to section 1.4.3-(4).)
0003
Overcurrent during
constant speed
operation
The load fluctuates abruptly.
The load is in an abnormal condition.
Reduce the load fluctuation.
Check the load (operated machine).
Low inductance motor especially High
speed motor is used.
Choose the higher power range drive.
(1 class up drive is recommended.)
The connecting cable length with a motor
is long.
AC reactors etc. are required for the
output side. (Refer to section 1.4.3-(4).)
0004
Overcurrent (An
overcurrent on the
load side at start-up)
The insulation of the output main circuit or
motor is defective.
The motor has too small impedance.
Check the secondary wiring and insulation
state.
Set
f613
=
2
,
3
0005
Overcurrent at start-
up
A main circuit element is defective.
Contact your Toshiba distributor.
*
0008
Input phase failure
A phase failure occured in the input line of
the main circuit.
The capacitor in the main circuit lacks
capacitance.
Check the main circuit input line for phase
failure.
Check the capacitor in the main circuit for
exhaustion.
*
0009
Output phase failure
A phase failure occurred in the output line
of the main circuit.
The motor has too big impedance.
Check the main circuit output line, motor,
etc. for phase failure.
Select output phase failure detection
parameter
f605
.
* This marking trips can be selected valid or invalid by parameters.