E6582175
K-4
11
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0007
Default setting
-
-
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Load user setting parameters
9. Cumulative fan operation time
record clears
10, 11: -
12: Number of starting clear
13: Default setting 2 (Complete
initialization)
0
4.3.2
0099
Checking the
region setting
* 5
-
-
0: Start setup menu
1: Japan (read only)
2: North America (read only)
3: Asia (read only)
4: Europe (read only)
*1
4.4
0050
EASY key mode
selection
-
-
0: Standard setting mode at power on
1: Easy setting mode at power on
2: Easy setting mode only
0
4.5
-
Extended parameter
starting at 100
-
-
-
-
-
4.2.2
-
Extended parameter
starting at 200
-
-
-
-
-
-
Extended parameter
starting at 300
-
-
-
-
-
-
Extended parameter
starting at 400
-
-
-
-
-
-
Extended parameter
starting at 500
-
-
-
-
-
-
Extended parameter
starting at 600
-
-
-
-
-
-
Extended parameter
starting at 700
-
-
-
-
-
-
Extended parameter
starting at 800
-
-
-
-
-
-
Extended parameter
starting at 900
-
-
-
-
-
-
Extended parameter
starting at A
-
-
-
-
-
-
Extended parameter
starting at C
-
-
-
-
-
-
Automatic edit
function
-
-
-
-
-
4.3.1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*5: Set “0” to activate the setup menu. Refer to section 11.5 about setting contents selected in setup menu.