E6582175
F-31
6
6.6.3
Changing the functions of VIA and VIB terminals
f109
: Analog/logic input selection (VIA/VIB)
Function
This parameter allows you to choose between analog signal input and contact signal input for the VIA
and VIB terminals.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f109
Analog/logic input
selection
(VIA/VIB)
0: VIA - analog input
VIB
-
analog input
0
1: VIA - analog input
VIB
-
contact input
2: -
3: VIA
-
contact input (Sink)
VIB
-
contact input
4: VIA
-
contact input (Source)
VIB
-
contact input
Note) When using VIA terminal as contact input terminals, be sure to insert a resistor between P24 terminal
and VIA terminal in sink logic connection, and insert a resistor between VIA terminal and CC terminal in
source logic connection. (Recommended resistance: 4.7k
-1/2W)
When using VIB terminal as contact input terminals, set the upper side of slide switch SW2 to S4 side
and then set
f109
.
Содержание TOSVERT VF-S15 series
Страница 394: ......