E6582175
K-2
11
Basic parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0003
Command mode
selection
-
-
0: Terminal block
1: Panel keypad (including extension
panel)
2: RS485 communication
3: CANopen communication
4: Communication option
1
3.2
6.2.1
7.3
0004
Frequency setting
mode selection 1
*13
-
-
0: Setting dial 1(save even if power is
off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to
save)
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14:
sro
0
3.2
6.2.1
6.10.1
5.8
7.3
0005
Meter selection
-
-
0: Output frequency
1: Output current
2: Frequency command value
3: Input voltage (DC detection)
4: Output voltage (command value)
5: Input power
6: Output power
7: Torque
8: -
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (Braking resistor) cumulative
load factor
12: Stator frequency
13: VIA input value
14: VIB input value
15: Fixed output 1
(output current 100% equivalent)
16: Fixed output 2
(output current 50% equivalent)
17: Fixed output 3
(Other than the output current)
18: RS485 communication data
19: For adjustments (
set value is
displayed.)
20: VIC input value
21, 22: -
23: PID feedback value
24: Integral input power
25: Integral output power
26-52: -
53: PBR (Braking resistor) load factor
0
5.1
0006
Meter adjustment
gain
-
-
-
-
0008
Forward/reverse
run selection
(Panel keypad)
-
-
0: Forward run
1: Reverse run
2: Forward run (F/R switching on
extension panel)
3: Reverse run (F/R switching on
extension panel)
0
6.2.2
*13: When setting the frequency by an extension panel option,
fmod
/
f207
is set to 0 or 3.