5) Overload characteristic selection
aul
Overload characteristic of inverter can be selected to 150%-60s or 120%-60s.
[Parameters settings]
Title
Function
Adjustment range
Default setting
aul
Overload characteristic selection
0: -
1: Constant torque
characteristic
(
150%-60s
)
2: Variable torque
characteristic
(
120%-60s
)
0
● Regarding to characteristic for
aul
=
1
setting, refer to section 5.6.3).
Note) In case of
aul
=
2
setting, be sure to install the input AC reactor (ACL) between power supply and inverter,
to remove the protective label on the top of the inverter, and to connect the grounding capacitors by
pressing the grounding capacitor switch.
Then, to use the inverter at 40°C or less of the ambient temperature with setting
f300
to 4.0 kHz or less.
aul
=
2
(Variable torque characteristic),
f631
=
0
(120%-60s)
Inverter overload protection characteristic
60
100%: Inverter rated output current
time
[s]
Inverter overload
Monitored output current [%]
0
105%
120%
Current
[%]
Inverter overload time [s]
(Outline data)
106
900
110
180
115
90
120
60
140
2
165
0.5