E6582175
K-7
11
Basic parameter 2
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0170
Base frequency 2
Hz
0.1/0.01
20.0-500.0
*1
6.8.1
0171
Base frequency
voltage 2
V
1/0.1
50-330 (240V class)
50-660 (500V class)
*1
0172
Torque boost
value 2
%
0.1/0.1
0.0-30.0
*2
0173
Motor electronic-
thermal protection
level 2
%
(A)
1/1
10-100 *12
100
5.6
6.8.1
6.29.1
0185
Stall prevention
level 2
%
(A)
1/1
10-199, *12
200 (disabled)
150
6.8.1
6.29.2
0190
V/f 5-point setting
VF1 frequency
Hz
0.1/0.01
0.0-
fh
0.0
6.3
6.9
0191
V/f 5-point setting
VF1 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0192
V/f 5-point setting
VF2 frequency
Hz
0.1/0.01
0.0-
fh
0.0
0193
V/f 5-point setting
VF2 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0194
V/f 5-point setting
VF3 frequency
Hz
0.1/0.01
0.0-
fh
0.0
0195
V/f 5-point setting
VF3 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0196
V/f 5-point setting
VF4 frequency
Hz
0.1/0.01
0.0-
fh
0.0
0197
V/f 5-point setting
VF4 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
0198
V/f 5-point setting
VF5 frequency
Hz
0.1/0.01
0.0-
fh
0.0
0199
V/f 5-point setting
VF5 voltage
%
(V)
0.1/0.1
0.0-125.0 *12
0.0
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*12: When
f701
=
1
, adjustment range is 100%=rated current, or 100%=200V(240V class)/ 400V(500V class).