E6582175
F-141
6
Title
Function
Adjustment range
Default setting
f856
Number of motor poles for
communication
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
2
f870
Block write data 1
0: No selection
1: Communication command 1
2: Communication command 2
3: Frequency command value
4: Output data on the terminal
block
5: FM analog output
6: Motor speed command
0
f871
Block write data 2
0
f875
Block read data 1
0: No selection
1: Status information 1
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal monitor
8: Output terminal monitor
9: Terminal VIA monitor
10: Terminal VIB monitor
11: Terminal VIC monitor
12: Input voltage (DC detection)
13: Motor speed
14: Torque
0
f876
Block read data 2
0
f877
Block read data 3
0
f878
Block read data 4
0
f879
Block read data 5
0
f899
Communication function reset
0: -
1: Reset (after execution: 0)
0
*1: Disabled ........... Indicates that the inverter will not be tripped even if a communication error occurs.
Trip ................... The inverter trips when a communication time-over occurs.
In this case a trip information
err5
flashes on and off on the operation panel.
Alarm ................ When a communication time-over occurs, an alarm can be output from the output terminal.
Output terminal function: 78 (RS485 communication error) or 79 (RS485 communication
error reverse)
*2: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Note2) Changes to the parameters
f800
,
f801
and
f806
do not take effect until the power is turned
off and then on again.