E6582175
F-134
6
6.34.8 Cancel the operation command
f719
: Selection of operation command clear
Function
This parameter allows you to select operation command retained or operation command cleared, when
coast stop occurs due to standby terminal function (ST), coast stop command terminal function (FRR),
and when under voltage in main circuit alarm (
moff
) occurs, during panel operation or RS485
communication operation.
Parameter
setting
At coast stop
At under voltage
in main circuit alarm (
moff
)
comd
is changed
=
Operation command
cleared
Operation command retained
=
Operation command retained
=
Operation command cleared
Operation command
retained
=
Operation command cleared
Operation command retained :
Inverter restarts due to clearing coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm (
)
occurs.
Operation command cleared :
Inverter doesn’t restart after coast stop or occurring the under voltage in main circuit alarm (
).
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title
Function
Adjustment range
Default setting
f719
Selection of operation
command clear
0: Clear at coast stop and retained at
moff
.
1: Retained at coast stop and
moff
.
2: Clear at coast stop and
moff
.
3: 2+ clear when
cmod
is changed
1
[Setup example of input terminal]
When it is assigned to the RES terminal.
Title
Function
Adjustment range
Setting
f113
Input terminal selection 3A
(RES)
0-203
6: ST (Standby)
f113
Input terminal selection 3A
(RES)
0-203
96: FRR (Coast stop command)
Setting value 7, 97 are reverse signal.
Содержание TOSVERT VF-S15 series
Страница 394: ......