E6582175
F-89
6
[Selection 2: Setting vector control and auto-tuning independently]
Set vector control, automatic torque boost, energy saving and auto-tuning individually.
After setting
pt
(V/F control mode selection), auto-tuning starts.
Set the auto-tuning parameter
f400
to
2
(Auto-tuning enabled)
[Parameter setting]
Title
Function
Adjustment range
Default setting
f400
Auto-tuning
0: Auto-tuning disabled
1: Initialization of
f402
(after execution : 0)
2: Auto-tuning executed
(after execution: 0)
3: -
4: Motor constant auto calculation
(after execution: 0)
5: 4+2 (after execution: 0)
0
Set
f400
to
2
before the start of operation. Auto-tuning is performed at the start of the motor and set
f402
,
f412
.
●
Precautions on auto-tuning
(1) Conduct auto-tuning after the motor has been connected properly and operation completely
stopped.
If auto-tuning is conducted immediately after operation stops, the presence of a residual voltage
may result in abnormal tuning.
(2) Voltage is applied to the motor during tuning even though it barely rotates. During tuning,
“
” is displayed on the operation panel.
(3) Tuning is performed when the motor starts for the first time after
f400
is set to
2
.
Tuning is usually completed within three seconds. If it is aborted, the inverter trips with the display
of
etn1
and no constants are set for that motor. Set
f400
to
0
and perform manual tuning
with selection 4.
(4) High-speed motors, high-slip motors or other special motors cannot be auto-tuned. For these
motors, perform manual tuning using Selection 3 described below.
(5) Provide cranes and hoists with sufficient circuit protection such as mechanical braking. Insufficient
motor torque while tuning may cause machine stalling/falling.
(6) If auto-tuning is impossible or an "
etn1
" auto-tuning error is displayed, perform manual tuning
with selection 4.
[Selection 3: Setting vector control and motor constant automatically]
After setting
vl
,
vlv
,
f405
,
f415
and
f417
, motor constants calculated automatically.
f402
,
f412
and
f416
are set automatically.
Set the motor constant parameter
f400
to
4
(auto calculation)
Set
f400
=
5
when auto-tuning is executed after setting motor constants automatically.