6.12.2 Motor shaft fixing control
f254
: Motor shaft fixing control
Function
This function is used to preheat the motor or to prevent the motor from running unexpectedly when its
shaft is not restrained.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f254
Motor shaft fixing control
0: Disabled, 1: Enabled
0
If the motor shaft fixing control
f254
is set to
1
, half amount of the braking force set with
f251
(DC
braking rate) will make the motor continue DC braking even after the completion of ordinary DC braking. To
stop motor shaft fixing control, turn off the standby command (ST signal).
DC injection braking start
frequency
LED
display
Time [s]
Output frequency [Hz]
Operation signal (F-CC)
ON
OFF
Output current [A]
0
0
Set frequency
Operation standby signal (ST-CC)
ON
OFF
2
“
” is displayed.
“
” is displayed.
As the default setting for ST (Standby) is Always ON, change the following settings:
(no function)
Assign 6: ST (Standby) to an open input terminal.