E6582175
D-11
4
60 Hz default setting (
typ
=
2
)
Setting
typ
to
2
sets the following parameters for base frequency 60 Hz use.
(The setting values of other parameters are not changed.)
• Maximum frequency (
fh
)
: 60Hz
• Upper limit frequency (
ul
) : 60Hz
• Base frequency 1 (
vl
)
: 60Hz
• Base frequency 2 (
f170
) : 60Hz
• VIA input point 2 frequency (
f204
) : 60Hz
• VIB input point 2 frequency (
f213
) : 60Hz
• VIC input point 2 frequency (
f219
) : 60Hz
• Automatic light-load high-speed operation
• Upper limit of set value (
f367
)
: 60Hz
frequency (
f330
) : 60Hz
• Motor rated speed (
f417
)
: 1710 min
-1
• Communication command point 2 frequency
(
f814
) : 60Hz
Default setting 1 (
typ
=
3
)
Setting
typ
to
3
will return parameters to the default settings (exclusive of some parameters).
● When
3
is set,
init
is displayed for a short time after the settings are configured, and then
disappears. Then the inverter is in standard motor mode. In this case, the trip history data is cleared.
Trip record clear (
typ
=
4
)
Setting
typ
to
4
initializes the past eight sets of recorded error history data.
● The parameter does not change.
Cumulative operation time clear (
typ
=
5
)
Setting
typ
to
5
resets the cumulative operation time to the initial value (zero).
Initialization of type information (
typ
=
6
)
Setting
typ
to
6
clears the trips when an
etyp
format error occurs. But if the
displayed, contact
your Toshiba distributor.
Be aware that the following parameters do not return to the default settings even if
typ
=
3
is set for
maintainability. (To initialize all parameters, set
typ
=
13
)
•
aul
:
Overload characteristic selection
•
f470
~
f475
:
VIA/VIB/VIC input bias / gain
•
fmsl
:
Meter selection
•
f669
:
Logic output/pulse train output selection
•
fm
:
Meter adjustment gain
•
f681
:
Analog output signal selection
•
set
:
Checking the region setting
•
f691
:
Inclination characteristic of analog output
•
f107
:
Analog input terminal selection
•
f692
:
Analog output bias
•
f109
:
Analog/logic input selection (VIA/VIB)
•
f750
:
EASY key function selection
•
f880
:
Free notes
* Refer to “Communication manual” about parameter
c
xxx.