E6582175
F-83
6
1)
External connection
2) Selecting PID set value and feedback value
PID set value and feedback value can be combined as follows for the PID control.
(1) PID set value
(2) Feedback value
PID set value signal selection
f389
PID control feedback signal selection
0:
fmod
/
f207
selected
1: Terminal VIA
2: Terminal VIB
3:
fpid
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
0: Disabled
1: Terminal VIA
2: Terminal VIB
3: Terminal VIC
4 to 6: -
Note 1: When setting
f389
, do not select the same signal used for feedback value.
Note 2: When
f389
=
3
is set, the PID set value is set by the parameter
fpid
.
fpid
can be set by the setting dial in the standard monitor mode.
Please inactivate the frequency setting by the setting dial (
fc
, Preset-speed frequency)
(Set
fmod
/
f207
to other than
0
or
3
,
f660
to other than
4
,
f724
to 0.)
Note 3: Signal is put out when the feedback value matches to the PID set value.
Assign function number 144 or 145 to an output terminal.
PID set value agreement detection range (
f167
) can also be set.
M
P
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
VIA
CC
Pressure
transmitter
(1) PID set
value
DC: 0 to 10V
(2)Feedback signals DC : 4~20mA
CC
VIC