E6582175
K-45
11
Table of output terminal functions 4
Function
No.
Code
Function
Action
Reference
144
PIDF
Signal in accordance of PID set value
ON: PID set value by
is within ±
of
.
OFF: Other than those above
6.24
145
PIDFN
Inversion of signal in accordance of PID set
value
Inversion of PIDF
146
FLR
Fault signal (output also at a retry waiting)
ON: While inverter is tripped or retried
OFF: While inverter is not tripped and not retried
6.19.3
147
FLRN
Inversion of fault signal (output also at a
retry waiting)
Inversion of FLR
150
PTCA
PTC input alarm signal
ON: PTC thermal input value is
f646
or more
OFF: PTC thermal input value is less than
f646
6.29.16
151
PTCAN
Inversion of PTC input alarm signal
Inversion of PTCA
152
STO
Safe torque off signal
ON: Opening terminals bSU and STO.
OFF: Shorting terminals bSU and STO.
7.2.2
153
STON
Inversion of safe torque off signal
Inversion of STO
154
DISK
Analog input break detection alarm
ON: VIC terminal input value is
f633
or less
OFF: VIC terminal input value is more than
f633
6.29.14
155
DISKN
Inversion of analog input break detection
alarm
Inversion of DISK
156
LI1
F terminal status
ON: F terminal is ON status
OFF: F terminal is OFF status
7.2.2
157
LI1N
Inversion of F terminal status
Inversion of LI1
158
LI2
R terminal status
ON: R terminal is ON status
OFF: R terminal is OFF status
159
LI2N
Inversion of R terminal status
Inversion of LI2
160
LTAF
Cooling fan replacement alarm
ON: Cooling fan reaches parts replacement time
OFF: Cooling fan does not reach parts replacement time
6.29.15
161
LTAFN
Inversion of cooling fan replacement alarm
Inversion of LTAF
162
NSA
Number of starting alarm
ON: Number of starting alarm is
f648
or more
OFF: Number of starting alarm is less than
f648
6.29.17
163
NSAN
Inversion of number of starting alarm
Inversion of NSA
166
DACC
Acceleration operation in progress
ON: Acceleration operation in progress
OFF: Other than those above
7.2.2
167
DACCN
Inversion of
acceleration operation in
progress
Inversion of DACC
168
DDEC
Deceleration operation in progress
ON: Deceleration operation in progress
OFF: Other than those above
169
DDECN
Inversion of
deceleration operation in
progress
Inversion of DDEC
170
DRUN
Constant speed operation in progress
ON: Constant speed operation in progress
OFF: Other than those above
171
DRUNN
Inversion of
constant speed operation in
progress
Inversion of DRUN
172
DDC
DC braking in progress
ON: DC braking in progress
OFF: Other than those above
6.12.1
173
DDCN
Inversion of
DC braking in progress
Inversion of DDC
174 to 179
Factory specific coefficient
-
*1
180
IPU
Integral input power pulse output signal
ON: Integral input power unit reach
OFF: Other than those above
6.33.1
182
SMPA
Shock monitoring pre-alarm signal
ON: Current / torque value reach the shock monitoring
detection condition
OFF: Other than those above
6.28
183
SMPAN
Inversion of
s
hock monitoring pre-alarm
signal
Inversion of SMPA
222 to 253
Factory specific coefficient
-
*1
254
AOFF
Always OFF
Always OFF
7.2.2
255
AON
Always ON
Always ON
*1: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Note 1: As function No. that are not described in the table above are assigned "No function", output signal is always “OFF” at
even number, output signal is always “ON” at odd number.