E6582175
F-80
6
1) To suspend acceleration or deceleration automatically
Set the frequency with
f350
or
f352
and the time with
f351
or
f353
, and then set
f349
to
1
.
When reached the set frequency, the motor stops accelerating or decelerating to run at a constant speed.
Output frequency [Hz]
Time [s]
2) To suspend acceleration or deceleration by means of a signal from an external control device
Set
60
for an input terminal. As long as ON signals are inputted, the motor continues to rotate at a constant
speed.
Output frequency [Hz]
Time [s]
Acceleration/deceleration
suspend signal
Ex.) When setting the acceleration/deceleration suspend signal to S3 terminal
Title
Function
Adjustment range
Example of setting
f116
Input terminal selection 6 (S3)
0-203
60 (Acceleration/
deceleration
suspend signal)
Function No. 61 is the inversion signal.
Note: If the operation signal is ON after Acceleration/ deceleration suspend signal is ON, the inverter will operate
at frequency set with
f240
.
If the stall control function is activated during constant-speed rotation
The frequency changes momentarily as a result of stall control, but the time for which the frequency changes is
included in the suspend time.