E6582175
F-60
6
(Input voltage above 480V)
VFS15-
Ambient
temperature
PWM carrier frequency
2.0k~4.0kHz
4.1k~12.0kHz
12.1k~16.0kHz
4004PL-W1
40
C or less
1.5 A
1.5 A
1.2 A
Above 40
50
C
1.5 A
1.5 A
1.2 A
Above 50
60
C
1.4 A
1.2 A
1.0 A
4007PL-W1
40
C or less
2.1 A
1.9 A
1.9 A
Above 40
50
C
2.1 A
1.9 A
1.9 A
Above 50
60
C
2.0 A
1.5 A
1.5 A
4015PL-W1
40
C or less
3.8 A
3.4 A
3.1 A
Above 40
50
C
3.8 A
3.4 A
3.1 A
Above 50
60
C
3.6 A
2.7 A
2.5 A
4022PL-W1
40
C or less
5.1 A
4.6 A
4.2 A
Above 40
50
C
5.1 A
4.6 A
4.2 A
Above 50
60
C
4.8 A
3.7 A
3.4 A
4037PL-W1
40
C or less
8.7 A
7.9 A
6.9 A
Above 40
50
C
8.7 A
7.9 A
6.9 A
Above 50
60
C
8.3 A
6.3 A
5.5 A
4055PL-W1
40
C or less
13.2 A
12.0 A
12.0 A
Above 40
50
C
13.2 A
12.0 A
12.0 A
Above 50
60
C
12.5 A
9.6 A
9.6 A
4075PL-W1
40
C or less
15.6 A
14.2 A
12.4 A
Above 40
50
C
15.6 A
14.2 A
12.4 A
Above 50
60
C
14.8 A
11.4 A
9.9 A
4110PL-W1
40
C or less
25.5 A
23.0 A
23.0 A
Above 40
50
C
25.5 A
23.0 A
23.0 A
Above 50
60
C
24.2 A
18.4 A
18.4 A
4150PL-W1
40
C or less
30.4 A
27.6 A
24.0 A
Above 40
50
C
30.4 A
27.6 A
24.0 A
Above 50
60
C
28.9 A
22.1 A
19.2 A
Note 1) : Inverter rated output current
(Carrier frequency 4kHz or less, ambient temperature 40
C or less )
Note 2) When ambient temperature is above 40
C, remove the protective label on the top of the inverter.
The condition of the load reduction (current reduction) on the table:
“Normal installation”. (Refer to 1.4.4)
For 40
C or less: with the top protective label
For above 40
C : without the top protective label