E6582175
F-77
6
● The drooping control function is to operate the power-running motor at operating frequency f
1
(Hz), which is
lower than command frequency f
0
(Hz) by droop frequency Δf (Hz), when the torque current is T
1
(%). (See
the figure above.)
The droop frequency Δf can be calculated using the following expression.
Droop frequency Δf (Hz)=base frequency
vl
×
f320
× (Torque current T
1
-
f323
)
When the torque current is above the specified droop insensitive torque band (
f323
), the frequency is
reduced during power running or increased during regenerative braking. The figure above shows an
example of the operating frequency during power running. During regenerative braking, control is
performed to increase the frequency.
The drooping control function is activated above the torque current set with
f323
.
The amount of droop frequency Δf varies depending on the amount of torque current T
1
.
Note: If the base frequency
vl
exceeds 100Hz, count it as 100Hz.
Control is exercised between the starting frequency (
f240
) and the maximum frequency (
fh
).
[An example of calculation]
Parameter setting: Base frequency
vl
=60 (Hz), droop gain
f320
=10 (%)
Droop insensitive torque band
f323
=30 (%)
Droop frequency Δf (Hz) and operating frequency f
1
when command frequency f
0
is 50 (Hz) and torque
current T
1
is 100 (%) are as follows;
Droop frequency Δf (Hz)=
vl
×
f320
× (T
1
-
f323
)
=60 (Hz) × 10 (%) × (100 (%) - 30 (%))
=4.2 (Hz)
Operation frequency f
1
(Hz) = f
0
- Δf = 50 (Hz) - 4.2 (Hz)=45.8 (Hz)
Power running