E6582175
F-111
6
6.29.10 Over-torque trip
f615
: Over-torque trip/alarm selection
f616
: Over-torque detection level
f618
: Over-torque detection time
f619
: Over-torque detection hysteresis
Function
If the torque value exceeds the value set at
f616
and doesn’t return below
f616
-
f619
for a time that exceeds the value set at
f618
, tripping or output alarm will be activated.
ot
is displayed in the event of a trip.
f615
=
0
: No tripping. (Failure signal FL not activated)
An over-torque alarm can be put out by setting the output terminal function selection parameter.
f615
=
1
: The inverter trips when a torque exceeding the
f616
-specified level has been detected for
longer than the
f618
-specified time. (Failure signal FL activated)
[Parameter setting]
Title
Function
Adjustment range
Default setting
f615
Over-torque trip/alarm selection
0: Alarm only
1: Tripping
0
f616
Over-torque detection level
0 (disabled), Note 1
1-320 (%)
150
f618
Over-torque detection time
0.0-10.0 (s) Note 2
0.5
f619
Over-torque detection hysteresis
0-100 (%)
10
Note 1: If
f616
is set to 0(disabled), the pre-alarm is not activated regardless of the
f615
setting.
Note 2:
f618
= 0.0 seconds is the shortest time detected on control.