E6582175
F-62
6
In case of
aul
=
2
(Variable torque characteristic (120%-60s)) setting.
VFS15-
Ambient
temperature
PWM carrier frequency
2.0k~4.0kHz
4004PL-W1
40
C or less
2.1 A
4007PL-W1
40
C or less
3.0 A
4015PL-W1
40
C or less
5.4A
4022PL-W1
40
C or less
6.9 A
4037PL-W1
40
C or less
11.1 A
4055PL-W1
40
C or less
17.0A
4075PL-W1
40
C or less
23.0 A
4110PL-W1
40
C or less
31.0A
4150PL-W1
40
C or less
38.0A
* In case of
=
2
setting, be sure to install the input AC reactor (ACL) between power supply and inverter,
to remove the protective label on the top of the inverter, and to connect the grounding capacitors by pressing
the grounding capacitor switch.
Then, to use the inverter at 40°C or less of the ambient temperature with setting
f300
to 4.0 kHz or less.
* If parameter
f316
=
0
,
2
or
4
and current is increased to main module overheat level (
ol3
) or to
overheat level (
oh
), the
l
alarm or
h
alarm occurs. If the cumulative amount of overload is increased further,
ol3
trip or
oh
trip occurs.
In this case, to avoid such trips, reduce the stall prevention level (
f601
) properly.
* PWM carrier frequency is increased at high output frequency area for stable operation, even if
f300
is set
to low PWM carrier frequency.