P9 ASD Installation and Operation Manual
205
MON1 Terminal Meter Selection
Program
Terminal
Analog Output Terminals
This parameter is used to set the output function of the
MON1
analog output
terminal. The available assignments for this output terminal are listed in
.
The
MON1
analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2 Instruction Manual
(P/N 58686) for
additional information on the function of this terminal.
MON1 Terminal Setup Parameters
— MON1 Output Function
— MON1 Terminal Meter Adjustment
— MON1 Voltage/Current Output Switching
— MON1 Output Gradient Characteristic
— MON1 Bias Adjustment Set Zero Level
Direct Access Number — F672
Parameter Type —
Selection List
Factory Default —
Output Voltage
Changeable During Run —
Yes
MON1 Terminal Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to set the gain of the
MON1
output terminal and is used
in conjunction with the settings of
.
See
for additional information on this parameter.
Direct Access Number — F673
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
MON2 Terminal Meter Selection
Program
Terminal
Analog Output Terminals
This parameter is used to set the output function of the
MON2
analog output
terminal. The available assignments for this output terminal are listed in
.
The
MON2
analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2 Instruction Manual
(P/N 58686) for
additional information on the function of this terminal.
MON2 Terminal Setup Parameters
— MON2 Output Function
— MON2 Terminal Meter Adjustment
— MON2 Voltage/Current Output Switching
— MON2 Output Gradient Characteristic
— MON2 Bias Adjustment Set Zero Level
Direct Access Number — F674
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......