P9 ASD Installation and Operation Manual
191
Speed 13 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 13
.
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F552
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
Setting
Speed 14 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 14
.
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F553
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
Setting
Speed 15 Operation Time
Program
Pattern Run
Operation Time
This parameter sets the run-time for
Preset Speed 15
.
This time is effective when used with
Group Speeds
and non-
Group Speeds
.
If the
Auto-Restart
function is activated, the search time required for the
Auto-
Restart
function will be subtracted from the
Operation Time
setting; resulting
in a shorter run time.
Direct Access Number — F554
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6000.0
Units —
Setting
Preset Speed Operation Mode
Program
Pattern Run
Operation Mode
This parameter is used to set the
Preset Speed
operating mode.
Select
Disabled
at this parameter to use the speed command only for
Preset
Speed
operation.
Select
Enabled
at this parameter to apply the control settings of
to
the associated
Preset Speed
while operating in the
Preset Speed
mode.
Settings:
0 — Disabled (Preset Speed Only)
1 — Enabled (Full Preset Speed Mode)
Direct Access Number — F560
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......