P9 ASD Installation and Operation Manual
155
(Virtual Linear Pump) Process Hold Operation Command
Value via the EOI
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation while operating
in the
Process Hold
mode and using the EOI for system control, this parameter
establishes the
Virtual Linear Pump
level.
This parameter setting is effective
ONLY
while operating in the
Process Hold
mode and while receiving a command via the EOI. The end value of this
parameter setting appears in the
Frequency Command
screen as shown below.
Direct Access Number — F397
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum —
Setting
Maximum —
Setting
(Virtual Linear Pump) Low Frequency Limit
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the
Virtual Linear Pump
Low Frequency Limit
.
Direct Access Number — F398
Parameter Type —
Numerical
Factory Default —
15
Changeable During Run —
Yes
Minimum — 1.00
Maximum — 60.00
Units — Hz
Autotuning 1
Program
Motor
Vector Motor Model
This parameter sets the
Autotune
command status.
Selecting
Reset Motor Defaults
for this parameter sets parameters
,
to the factory default settings.
If selecting
Autotune on Run Command
,
Autotune Initiated by Input
Terminal
, or
Autotune of Detail Parameters
for this parameter, set the
Base
Frequency
,
Base Frequency Voltage
, and the
Motor Rated Revolutions
to
the nameplated values of the motor to achieve the best possible
Autotune
precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see
)
4 — Motor Constant Auto Calculation
Direct Access Number — F400
Parameter Type —
Selection List
Factory Default —
Autotune Disabled
Changeable During Run —
No
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...