P9 ASD Installation and Operation Manual
121
BIN Input Point 1 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
BIN
input terminals when
the
BIN
terminals are used as the control input while operating in the
Speed
Control
mode.
The discrete input terminals of the
Terminal Board
are used as the
BIN
terminals.
BIN Input Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
BIN
input terminals:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
Binary/BCD
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Block
.
• Program
Terminal
Input Terminals
; select and set the desired
discrete input terminals to
Binary Bit
(s)
0 – 7
(or 0 – MSB). The binary
input byte will control the speed of the motor.
• Program
Terminal
Input Terminals
; select and set a discrete input
terminal to
Binary Data Write
. Activation of the
Binary Data Write
terminal will transfer the status of the
Binary Bit
(s)
0 – 7
(or 0 – MSB) to
the control board for speed control.
Speed Control
Perform the following setup to allow the system to perform
Speed
control from
the
BIN
input terminals:
• Set
BIN Input Point 1 Frequency
• Set the
BIN
input value (% of 255
D
) (
) that represents
BIN Input
Point 1 Frequency
.
• Set
BIN Input Point 2 Frequency
• Set the
BIN
input value (% of 255
D
) (
) that represents
BIN Input
Point 2 Frequency
.
• Provide a
Run
command (F and/or R).
Note:
255
D
is the decimal equivalent of the 8-bit BIN byte with all input
terminals set to 1 (255 decimal = 11111111 binary).
Once set, as the
BIN
input signal changes are transferred to the control board,
the output frequency of the ASD will vary in accordance with the above
settings.
This parameter sets
BIN Input Point 1 Setting
and is entered as 0% to 100%
of the range represented by the
BIN
binary input byte 11111111 (255
D
) or the
binary bit(s) 0 – MSB.
Direct Access Number — F228
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......