82
P9 ASD Installation and Operation Manual
Upper-Limit Frequency
Program
Fundamental
Frequency Settings
This parameter sets the highest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD may output frequencies
higher than the
Upper-Limit Frequency
(but, lower than the
Maximum
Frequency
) when operating in the
PID Control
mode,
Torque Control
mode,
or the
Vector Control
modes (sensorless or feedback).
Note:
This setting may not be higher than the
Maximum Frequency
(
)
setting.
Direct Access Number — F012
Parameter Type —
Numerical
Factory Default —
66.0
Changeable During Run —
Yes
Minimum — Lower-Limit Freq. (
)
Maximum — Maximum Freq. (
Units — Hz
Lower-Limit Frequency
Program
Fundamental
Frequency Settings
This parameter sets the lowest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD will output frequencies
lower than the
Lower-Limit Frequency
when accelerating to the lower-limit or
decelerating to a stop. Frequencies below the
Lower-Limit
may also be output
when operating in the
PID Control
mode,
Torque Control
mode, or the
Vector Control
modes (sensorless or feedback).
Direct Access Number — F013
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (
Units — Hz
Base Frequency 1
Program
Fundamental
Motor Set 1
The
Base Frequency 1
setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The
Base Frequency Voltage 1
parameter is set at
For proper motor operation, the
Base Frequency
should be set for the
nameplated frequency of the motor.
Direct Access Number — F014
Parameter Type —
Numerical
Factory Default —
60.0
Changeable During Run —
No
Minimum — 0.0
Maximum — Upper-Limit Freq. (
Units — Hz
V/f Pattern
Program
Fundamental
Frequency Settings
This function establishes the relationship between the output frequency and the
output voltage.
Bolded
selections use the motor tuning parameters of the ASD to properly
configure the ASD for the motor being used. If
Load Reactors
or
Long Lead
Filters
are used, or if the capacity of the ASD is greater than the motor, manual
tuning of the motor parameters may be required for optimum performance.
Settings:
0 — Constant Torque
1 — Voltage Decrease Curve
2 —
Automatic Torque Boost
3 —
Sensorless Vector Control (Speed)
4 —
Sensorless Vector Control (Speed/Torque Switching)
to configure the V/f 5-Point Settings)
6 — PM Drive (Permanent Magnet)
7 —
PG Feedback Vector Control (Speed)
8 —
PG Feedback Vector Control (Speed/Torque Switching)
Note:
When operating in the
Vector Control
mode the carrier
frequency should be set to 2.2 kHz or above.
Direct Access Number — F015
Parameter Type —
Selection List
Factory Default —
Automatic Torque
Boost
Changeable During Run —
No
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......