P9 ASD Installation and Operation Manual
107
V/I Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
V/I Input Point 1 Frequency
and is the frequency that is
associated with the setting of
V/I Input Point 1 Setting
when operating in the
Speed Control
mode.
See
V/I Input Point 1 Setting
) for additional information on this
parameter.
Direct Access Number — F202
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
V/I Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Speed
Control
mode
or the
Torque Control
mode.
This parameter sets the
V/I
input level that is associated with
V/I Input Point 2
Frequency
when operating in the
Speed
control mode or is associated with the
V/I Input Point 1 Rate
when operating in the
Torque Control
mode.
This value is entered as 0% to 100% of the
V/I
input signal range.
See
V/I Input Point 1 Setting
) for additional information on this
parameter when used for
Speed
control.
See
V/I Input Point 1 Rate
) for additional information on this parameter
when used for
Torque
Control
.
Direct Access Number — F203
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
V/I Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Speed
Control
mode.
This parameter sets
V/I Input Point 2 Frequency
and is the frequency that is
associated with the setting of
V/I Input Point 2 Setting
when operating in the
Speed Control
mode.
See
V/I Input Point 1 Setting
) for additional information on this
parameter.
Direct Access Number — F204
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......