P9 ASD Installation and Operation Manual
151
(Virtual Linear Pump) Sleep Timer Delay
Virtual Linear Pump
Sleep Timer Setting
During a properly configured
Virtual Linear Pump
operation, and once
, this parameter establishes the time that system operation will
be allowed to operate within the
threshold
before the ASD output to the motor is terminated.
See
for additional information on this parameter.
Direct Access Number — F383
Parameter Type —
Numerical
Factory Default —
300
Changeable During Run —
Yes
Minimum — 1
Maximum — 63335
Units — Seconds
(Virtual Linear Pump) Direct Operation Command Value
Program
Virtual Linear Pump
Virtual Linear Pump Settings
During a properly configured
Virtual Linear Pump
operation while operating
in the
Direct
mode and using the EOI for system control, this parameter
establishes the
Virtual Linear Pump
level.
This parameter setting is effective
ONLY
while operating in the
Direct
mode
and while receiving a command from the EOI. The end value of this parameter
setting appears in the
Frequency Command
screen as shown below.
Direct Access Number — F384
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 10
Maximum — 165
(Virtual Linear Pump) Auto Start-Stop Mode
Virtual Linear Pump
Auto Start-Stop Mode Enable
During a properly configured
Virtual Linear Pump
operation, this parameter
Enables/Disables
the ability of the system to receive transducer input to
manage system starts and stops as it pertains to the process variable.
This parameter is also used to select the ASD response (Stop or Start) upon
meeting the criteria of
and
settings.
On Forward
= Run ASD while measured signal is
setting and stop
setting.
On Reverse
= Run ASD while measured signal is
setting and stop ASD
setting.
Settings:
0 — Off
1 — On Forward
2 — On Reverse
Direct Access Number — F385
Parameter Type —
Selection List
Factory Default —
Off
Changeable During Run —
Yes
WARNING
The Auto Start-Stop operating mode may result in the
unexpected Start or Stop of the motor. Signs to this effect are
to be posted at the location of the motor/pump.
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......