152
P9 ASD Installation and Operation Manual
(Virtual Linear Pump) Auto Start-Stop Delay Timer
Virtual Linear Pump
Auto Start-Stop Delay Timer
During a properly configured
Virtual Linear Pump
operation, this parameter
establishes the time that the
Start-Stop
and
must be
maintained to activate the
Auto Start-Stop
function.
This feature is used to minimize system responses to rapid fluctuations in the
feedback signal.
See
for additional information on this parameter.
Direct Access Number — F387
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
Yes
Minimum — 0.1
Maximum — 6553.5
Units — Seconds
(Virtual Linear Pump) Auto Start-Stop Lower Threshold
Virtual Linear Pump
Auto Start-Stop Threshold Setting
During a properly configured
Virtual Linear Pump
operation while in the
On
Forward
or
On Reverse
modes (
), this parameter establishes the lower
level of the
Auto Start-Stop
threshold.
See
for additional information on this parameter.
The unit of measure for this parameter may be one of the following types — the
type is selected while running the
Virtual Linear Pump Setup Wizard
.
• PSI
• GPM
• Inches of Water Column
• Feet of Water Column
• CFM
• °C
• °F
• Custom
(Custom selection allows for three character spaces to be populated from the 26
alphabet and 13 special characters)
Direct Access Number — F388
Parameter Type —
Numerical
Factory Default —
Application-Specific
Changeable During Run —
Yes
Minimum —
Setting
Maximum —
Setting
Units — Selectable at Wizard
(Virtual Linear Pump) Auto Start-Stop Upper Threshold
Virtual Linear Pump
Auto Start-Stop Threshold Setting
During a properly configured
Virtual Linear Pump
operation while in the
On
Forward
or
On Reverse
modes (
), this parameter establishes the upper
level of the
Auto Start-Stop
threshold.
See
for additional information on this parameter.
The unit of measure for this parameter may be one of the following types — the
type is selected while running the
Virtual Linear Pump Setup Wizard
.
• PSI
• GPM
• Inches of Water Column
• Feet of Water Column
• CFM
• °C
• °F
• Custom
(Custom selection allows for three character spaces to be populated from the 26
alphabet and 13 special characters)
Direct Access Number — F389
Parameter Type —
Numerical
Factory Default —
300.0
Changeable During Run —
Yes
Minimum —
Setting
Maximum —
Setting
Units — Selectable at Wizard
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......