P9 ASD Installation and Operation Manual
PG Disconnection Detection
Program
Feedback
PG Settings
This parameter
Enables/Disables
the system’s monitoring of the PG
connection status when using encoders with line driver outputs.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Settings:
0 — Disabled
1 — Enabled with Filter
3 — Enabled (Detect momentary power fail)
Direct Access Number — F377
Parameter Type —
Selection List
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
(Virtual Linear Pump) Application Operating Mode
Program
Virtual Linear Pump
Virtual Linear Pump Settings
While operating in the
Virtual Linear Pump
mode, this parameter sets the
system response to the received feedback from the
V/I
terminal.
Select
Direct Acting
to produce an increase in the ASD output with a decrease
in the feedback signal.
Select
Reverse Acting
to produce a decrease in the ASD output with a decrease
in the feedback signal.
Settings:
0 — Direct Acting (Positive Gradient)
1 — Reverse Acting (Negative Gradient)
Direct Access Number — F380
Parameter Type —
Selection List
Factory Default —
Direct Acting
Changeable During Run —
No
Simple Positioning Completion Range
Program
Feedback
PG Settings
While operating in the
Positioning Control
mode, this parameter sets the range
of accuracy for a
Stop
command initiated via the terminal board.
If the setting is too low, the stop may be too abrupt.
Direct Access Number — F381
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 1
Maximum — 4000
(Virtual Linear Pump) Sleep Timer
Virtual Linear Pump
Sleep Timer Enable
During a properly configured
Virtual Linear Pump
operation, this parameter
Enables/Disables
the ability of the ASD to terminate the output signal to the
motor upon operating for a user-set amount of time within the
threshold.
See
for additional information on this parameter.
Settings:
0 — Disabled
1 — Enabled
Direct Access Number — F382
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
Yes
WARNING
The Sleep Timer function may result in the unexpected Start
or Stop of the motor. Signs to this effect are to be posted at
the location of the motor/pump.
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......