Regenerative Braking Torque Limit 4 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the
4
motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Set this parameter to
250%
to disable this function.
Direct Access Number — F449
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
(Virtual Linear Pump) Low Suction/No-Flow Cut Off Fault
Disposition
Program
Virtual Linear Pump
Low Suction/No-Flow Cut Off
This parameter is used in conjunction with the setting of
If
On (Physical Switch)
or
On (Electronic Switch)
, then
this parameter selection sets the disposition of the system in the event of a
Low
Suction
/
No-Flow
Cut Off
condition that exists for the duration of the
setting.
If
Off
, then this parameter selection is ignored.
Settings:
0 — Trip
1 — Alarm
2 — Alarm and Restart at
Interval
Direct Access Number — F450
Parameter Type —
Selection List
Factory Default —
Trip
Changeable During Run —
Yes
Accel/Decel Operation After Torque Limit
Program
Torque
Torque Limit Settings
In a Crane/Hoist application that is operating using a mechanical brake, this
parameter is used to minimize the delay between the brake release and the
output torque reaching a level that can sustain the load.
This setting may reference time or the operating speed of the motor.
Settings:
0 — In Sync with Accel/Decel
1 — In Sync with Minimum Time
Direct Access Number — F451
Parameter Type —
Selection List
Factory Default —
In Sync with Accel/
Decel
Changeable During Run —
Yes
Power Running Stall Continuous Trip Detection Time
Program
Protection
Stall
This parameter is used to extend the
Over-Voltage
Stall
(
and the
Over-
Current Stall
(
) time settings.
Direct Access Number — F452
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 1.0
Units — Seconds
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......