218
P9 ASD Installation and Operation Manual
Point 2 Frequency
Program
Communications
Communication Reference Adjust
This parameter is used to set the gain and bias of the
Communications
Reference
speed control input.
See
for additional information on this parameter.
This parameter sets the
Communications Reference Speed Setpoint 2
.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F814
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Baud Rate (RS485)
Program
Communications
Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
Direct Access Number — F820
Parameter Type —
Selection List
Factory Default —
19200
Changeable During Run —
Yes
RS485 Send Delay (4-Wire RS485)
Program
Communications
Communication Settings
This parameter sets the
RS485
response delay time.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F825
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......