248
P9 ASD Installation and Operation Manual
138 139
Low Suction/No Flow Protection
—
Will not allow the ASD to start if activated, or terminates the ASD output
upon activation (if running) in the event of the loss of feed water or a closed output valve at the pump output.
140 141
Sealing Water
—
Once an adequate water supply is detected at the pump seal via a reed switch, activation enables
the ASD for normal operations.
142 143
Virtual Linear Pump Enable/Disable
—
Activation enables the
Virtual Linear Pump
function for normal
operation. The
Virtual Linear Pump
function is disabled when the terminal is not active.
144 145
ON Float
—
Activation runs the ASD at the setting of
146 147
OFF Float
—
Activation has a dual function:
1) Changes the operating mode from
Process Hold
to
Direct
.
2) Turns off the ASD.
148 149
Trigger Float
—
Activation changes the operating mode from
Process Hold
to
Direct
.
150 151
Alarm Float
—
This input is typically connected to a float switch that, when activated, annunciates that the fluid level
is now critical. The discrete output terminals
OUT1
and/or
OUT2
may be associated with the activation (set
OUT1
/
OUT2
to
TBA Alarm Float
to activate an auxiliary system — i.e., aux pump, relief valve, audible/visual alarm, etc.).
152 153
TBA HOA Switch
—
Activation enables
Time-Based Alternation
operation. Operates in conjunction with the
setting of
.
NO/NC = Normally Open/Normally Closed.
*Selection numbers are used when configuring the ASD via communications. The Normally Open (NO) or Normally
Closed (NC) configuration must be chosen by selecting the associated number.
Table 6. Discrete Input Terminal Assignment Selections and Descriptions. (Continued)
*Sel. No.
Terminal Selection Descriptions
NO NC
Sealing Water
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......