118
P9 ASD Installation and Operation Manual
RX2 (AI1) Input Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode.
This parameter sets
RX2
(AI1)
Input Point 1 Frequency
and is the frequency
that is associated with the setting of
RX2
(AI1)
Input Point 1 Setting
when
operating in the
Speed Control
mode.
See
RX2
(AI1)
Input Point 1 Setting
(
) for additional information on this
parameter.
Direct Access Number — F223
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
RX2 (AI1) Input Point 2 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode or the
Torque Control
mode.
This parameter sets the
RX2
(AI1) input level that is associated with
RX2
(AI1)
Input Point 2 Frequency
when operating in the
Speed
control mode or
is associated with the
RX2
(AI1)
Input Point 2 Rate
when operating in the
Torque Control
mode.
This value is entered as -100% to +100% of the
RX2
(AI1) input signal range.
See
RX2
(AI1)
Input Point 1 Setting
(
) for additional information on this
parameter when used for
Speed
control.
See
RX2
(AI1)
Input Point 1 Rate
) for additional information on this
parameter when used for
Torque Control
.
Direct Access Number — F224
Parameter Type —
Numerical
Factory Default —
+100
Changeable During Run —
Yes
Minimum — -100
Maximum — +100
Units — %
RX2 (AI1) Input Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode.
This parameter sets
RX2
(AI1)
Input Point 2 Frequency
and is the frequency
that is associated with the setting of
RX2
(AI1)
Input Point 2 Setting
when
operating in the
Speed Control
mode.
See
RX2
(AI1)
Input Point 1 Setting
(
) for additional information on this
parameter.
Direct Access Number — F225
Parameter Type —
Numerical
Factory Default —
60.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......