P9 ASD Installation and Operation Manual
117
RX2 (AI1) Input Point 1 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the
RX2
(AI1) input terminal
when the
RX2
(AI1) terminal is used as the control input while operating in the
Speed Control
mode or the
Torque Control
mode.
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
This parameter sets the
RX2
(AI1) input level that is associated with
RX2
(AI1)
Input Point 1 Frequency
when operating in the
Speed
Control
mode or
is associated with the
RX2
(AI1)
Input Point 1 Rate
when operating in the
Torque
Control
mode.
RX2 (AI1) Input Speed Control Setup
Perform the following setup to allow the system to receive
Speed
control input
at the
RX2
(AI1) input terminal:
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
RX2
.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Block
.
Speed Control
Perform the following setup to allow the system to perform
Speed
control from
the
RX2
(AI1) input terminal:
• Set
RX2
(AI1)
Input Point 1 Frequency
(
).
• Set
RX2
(AI1)
Input Point 1 Setting
(
) — the input analog signal
level that corresponds to the speed setting at
RX2
(AI1)
Input Point 1
Frequency
.
• Set
RX2
(AI1)
Input Point 2 Frequency
(
).
• Set
RX2
(AI1)
Input Point 2 Setting
(
) — the input analog signal
level that corresponds to the speed setting at
RX Input Point 2 Frequency
.
• Provide a
Run
command (F and/or R).
Once set, as the
RX2
(AI1) input voltage changes, the ASD output speed and/or
torque will vary in accordance with the above settings.
This parameter value is entered as -100% to +100% of the
RX2
(AI1) input
signal range.
See the
Expansion IO Card Option 1 Instruction Manual
(P/N 58685) for
additional information on the function of this terminal. See
for
information on fine-tuning this terminal response.
Direct Access Number — F222
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — -100
Maximum — +100
Units — %
Frequency Settings
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......