P9 ASD Installation and Operation Manual
105
V/f 5-Point Setting Frequency 5
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Frequency 5
sets the frequency to be associated with
the voltage setting of parameter
(V/f 5-Point Setting Voltage 5).
See
for additional information on this parameter.
Direct Access Number — F198
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
No
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
V/f 5-Point Setting Voltage 5
Program
Special
V/f 5-Point Setting
The
V/f 5-Point Setting Voltage 5
establishes the output voltage level that is to
be associated with the frequency setting of
(V/f 5-Point Setting
Frequency 5).
setting will determine if the selection for this parameter appears in
the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
for additional information on this parameter.
Direct Access Number — F199
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 100.0
Units — V or % (
)
Frequency Priority Selection
Program
Fundamental
Standard Mode Selection
Either
Frequency Mode 1
or
Frequency Mode 2
may control the output
frequency of the ASD. This parameter determines which of the two will control
the output frequency and the conditions in which control will be switched from
one to the other.
Note:
Frequency Mode
is abbreviated as
FMOD
.
The
Frequency Mode 1
or
Frequency Mode 2
selection specifies the source of
the input frequency command signal. These selections are performed at
and
, respectively.
If
FMOD changed by Terminal Board
is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of
Frequency
Priority
. The discrete terminal
Frequency Priority
will toggle control to and
from
Frequency Mode 1
and
Frequency Mode 2
with each activation/
deactivation.
If
FMOD
)
is selected here, the ASD will follow the control of the
Frequency Mode 1
setting for the duration that the commanded frequency of
the
Frequency Mode 1
setting is greater than the setting of
. If the
commanded frequency of the
Frequency Mode 1
setting is less than or equal to
the setting of
, the ASD will follow the setting of
Frequency Mode 2
.
Settings:
0 — FMOD changed by Terminal Board (Frequency Mode)
1 — FMOD (
) (Frequency Mode)
Direct Access Number — F200
Parameter Type —
Selection List
Factory Default —
FMOD (changed by
Terminal Board)
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......