P9 ASD Installation and Operation Manual
109
V/I Input Point 2 Rate
Program
Torque
Setpoints
This parameter is used to set the gain and bias of the
V/I
input terminal when
the
V/I
terminal is used as the control input while operating in the
Torque
Control
mode.
Torque Control is accomplished by establishing an associated
V/f
output pattern
for a given
V/I
input level.
This parameter sets
V/I Input Point 2 Rate
and is the output torque value that
is associated with the setting of
V/I Input Point 2 Setting
when operating in
the
Torque Control
mode.
This value is entered as 0% to 250% of the rated torque.
See
V/I Input Point 1 Rate
(
) for additional information on this
parameter.
Direct Access Number — F206
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Frequency Mode 2
Program
Fundamental
Standard Mode Selection
This parameter is used to set the source of the frequency command signal to be
used as
Frequency Mode 2
in the event that
Frequency Mode 1
is disabled or
if
Frequency Mode 2
is set up as the primary control parameter.
See
for additional information on this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
5 — EOI (Keypad)
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 —
Option V/I
10 — UP/DOWN Frequency (Terminal Board)
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
Direct Access Number — F207
Parameter Type —
Selection List
Factory Default —
V/I
Changeable During Run —
Yes
Frequency Mode Priority Switching Frequency
Program
Fundamental
Standard Mode Selection
This parameter
establishes a threshold frequency that will be used as a reference
when determining when to switch the output frequency control source from the
Frequency Mode 1
setting to the
Frequency Mode 2
setting.
See
for additional information on this parameter.
Direct Access Number — F208
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.10
Maximum — Maximum Freq. (
Units — Hz
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......