P9 ASD Installation and Operation Manual
243
My Function Selection
Program
My Function
This parameter
Enables/Disables
the configured
My Function
feature of the
P9 ASD.
Settings:
0 — None (Disabled)
1 — My Function with Terminal Board Signal (discrete terminal activation)
2 — My Function Always On
My Function
The
My Function
feature is configured using the settings of
and
is used to enhance the programmability of the P9 ASD by performing two
programmable functions: 1) the Combined Terminal Function, and 2) Logic
Operations.
Combined Terminal Function
Assigning more than one function to a discrete output terminal provides two
advantages: it effectively expands the number of input terminals, and it reduces
the number of cables required to support the input/output functions (e.g.,
assigning ST and F to one terminal). Using
Virtual Terminals 1
–
4
–
) is required to use this function.
In the example below, the
ST
terminal assignment and the
F
terminal
assignment will be combined as one terminal to illustrate this feature. However,
any two of the discrete output terminal assignments listed in
may be combined in this manner.
Setup (Example)
1.
Disable the
My Function
parameter at
to prevent the system from
starting upon completion of the setup.
2.
Assign the
ST
function to the
S1
terminal (
).
3.
Assign the
F
function to
Virtual Input Terminal 1
).
4.
Set
Input Function Target 1
to
5
(
). This setting assigns
S1
as the
control input terminal.
5.
Set
Output Function Assigned
to
21
). This setting is a command
that writes the
F115
selection (S1) to
Virtual Input Terminal 1
, activating
both.
6.
Enable the
My Function
parameter at
by selecting
My Function
Always On
or selecting
My Function With TB Signal
.
If set to
My Function Always On
, the combination of
ST
and
F
are
always On (both are connected to CC only during the S1
activation).
If set to
My Function With TB Signal
, set a discrete input terminal
to
My Function Run Signal
and connect it to
CC
to enable
My
Function
. Connect
S1
to
CC
to activate the
ST+F
function. A
disconnection at either terminal will terminate the
My Function
programming (discrete input terminal
My Function Run Signal
is
Anded with discrete input terminal
S1
).
Connect
S1
to
CC
and the
F
-to-
CC
+ the
ST
-to-
CC
functions will be carried
out using only
S1
.
With the aforementioned setup completed, provide a
Frequency Command
) and the motor will run at the commanded frequency.
Continued on next page.
Direct Access Number — F977
Parameter Type —
Selection List
Factory Default —
None (Disabled)
Changeable During Run —
No
This parameter must always be set to
None
at the start of the
My Function
setup and remain set to
None
until all
of the
My Function
parameter
settings have been confirmed as
being correct.
If enabled for normal operation using
settings
1
or
2
, the motor may start
and engage the driven equipment
unexpectedly upon receiving a
Run
signal during the
My Function
setup.
DANGER
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......