P9 ASD Installation and Operation Manual
Output Terminal 9 (R2) Function
Program
Terminal
Output Terminals
This parameter is used to set the functionality of the
R2
discrete output
terminal.
In addition, this output terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
R2
terminal to one of the
user-selectable functions listed in
Note:
The
Expansion IO Card Option 2
option board (P/N ETB004Z)
is required to use this terminal.
See the
Expansion IO Card Option 2 Instruction Manual
(P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F138
Parameter Type —
Selection List
Factory Default —
Always Off
Changeable During Run —
No
Input Terminal 1 (F) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
F
terminal
input by the programmed value.
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F140
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 2 (R) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
R
terminal
input by the programmed value (see waveforms at
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F141
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 3 (ST) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
ST
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F142
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......