140
P9 ASD Installation and Operation Manual
Synchronized Acceleration Time
Program
Protection
Under-Voltage/Ridethrough
In the event that the
Ridethrough
function activates in a multiple-motor
application, it will be necessary to manage the accelerating motors
synchronously as not to damage the product being processed (e.g., wire spools,
bobbin winder for textile machines, etc.).
This parameter is used to minimize the product breakage during a momentary
power outage. This function orchestrates the acceleration of multiple machines
simultaneously or makes them reach their respective command frequencies
simultaneously by regulating their acceleration times.
See
for additional information on this parameter.
Direct Access Number — F318
Parameter Type —
Numerical
Factory Default —
2.0
Changeable During Run —
Yes
Minimum — 0.10
Maximum — 6000
Units — Seconds
Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the effective 100% output torque level while operating in
the
Drooping Control
mode. This value is the upper torque limit of the motor
being driven by a given ASD while operating in the
Drooping Control
mode.
Note:
The maximum frequency output is not limited by the setting of
while operating in the
Drooping Control
mode.
Drooping
Drooping
Control
, also called
Load Share
, is used to share the load among
two or more mechanically coupled motors. Unlike
Stall
, which reduces the
output frequency in order to limit the load once the load reaches a preset level,
Drooping
can decrease or increase the V/f setting of a motor to maintain a
balance between the output torque levels of mechanically coupled motors.
Because of variances in gearboxes, sheaves, belts, motors, and since the speed
of the motor is constrained by the mechanical system, one motor may
experience more load than its counterpart and become overloaded.
Drooping
Control
allows the overloaded motor to slow down, thus shedding load and
encouraging a lightly-loaded motor to pick up the slack. The goal of
Drooping
Control
is to have the same torque ratios for mechanically coupled motors.
Direct Access Number — F320
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Speed at 0% Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the motor speed when at the 0% output torque gain while
operating in the
Drooping
Control
mode. This function determines the lowest
speed that
Drooping
will be in effect for motors that share the same load.
Direct Access Number — F321
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 320.0
Units — Hz
Drooping Gain
Program
Feedback
Drooping Control
This parameter sets the motor speed when at the 100% output torque gain while
operating in the
Drooping
Control
mode. This function determines the speed
of the individual motors at the 100%
Drooping Gain
setting for motors that
share the same load.
Direct Access Number — F322
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 320.0
Units — Hz
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......