98
P9 ASD Installation and Operation Manual
Input Terminal 19 (B14) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
B14
discrete input
terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
B14
terminal to any one
of the user-selectable functions listed in
.
See the
My Function
Instruction Manual
(P/N E6581335) for additional
information on the function of this terminal.
Direct Access Number — F166
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Input Terminal 20 (B15) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
B15
discrete input
terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
B15
terminal to any one
of the user-selectable functions listed in
.
See the
My Function
Instruction Manual
(P/N E6581335) for additional
information on the function of this terminal.
Direct Access Number — F167
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Output Terminal 10 (R3) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
R3
output terminal to any one of the
user-selectable functions listed in
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
See the instruction manual for the
16-Bit BIN/BCD
option for additional
information on the function of this terminal.
Direct Access Number — F168
Parameter Type —
Selection List
Factory Default —
OFF
Changeable During Run —
No
Output Terminal 11 (R4) Function
Program
Terminal
Output Terminals
This parameter sets the functionality of the
R4
output terminal to any one of the
user-selectable functions listed in
In addition, the output terminals must be specified as
Normally Open
or
Normally Closed
.
See the instruction manual for the
16-Bit BIN/BCD
option for additional
information on the function of this terminal.
Direct Access Number — F169
Parameter Type —
Selection List
Factory Default —
OFF
Changeable During Run —
No
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......