P9 ASD Installation and Operation Manual
219
ASD-to-ASD Communications (RS485)
Program
Communications
Communication Settings
The function of this parameter is two-fold:
1) In a Master/Follower configuration and while communicating via RS485
4-wire, this parameter sets the ASD as the Master or the Follower.
2) This parameter determines the function of the ASD while operating as the
Master or the Follower. If operating as the Master ASD, an output parameter
of the Master ASD is used to control the Follower ASDs and is set here. If
operating as a Follower ASD, the ASD response when an error is incurred is
set here.
Note:
Select a Follower function here if
is configured as a
Master
Output
controller for any other ASD in the system. Otherwise, an
EOI
failure will result.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — Follower (Decel Stop if Error Detected)
1 — Follower (Continues Operation if Error Detected)
2 — Follower (Emergency Off if Error Detected)
3 — Master (Frequency Command)
4 — Master (Output Frequency)
5 — Master (Torque Reference)
6 — Master (Output Torque)
Direct Access Number — F826
Parameter Type —
Selection List
Factory Default —
Follower (Decel Stop)
Changeable During Run —
Yes
RS485 Protocol Selection
Program
Communications
Communication Settings
This parameter sets the communications protocol for ASD-to-ASD
communications.
Settings:
0 — Toshiba
1 — Modbus
2 — BACnet
Direct Access Number — F829
Parameter Type —
Selection List
Factory Default —
Toshiba
Changeable During Run —
Yes
Communications Option (DeviceNet/Profibus) Setting 1
Program
Communications
Communication Settings
While using the DeviceNet/Profibus communications protocol, this parameter
allows the user to select the read and write information communicated between
the ASD and the Host.
Read information may include the ASD fault status, ASD speed, ASD MAC
ID, etc. Write information may include Enable/Disable DeviceNet commands,
Forward run, ACC/DEC command, etc.
See the
DeviceNet Option Instruction Manual
(P/N 58683) for additional
information on this parameter.
Settings:
0 – 7
Direct Access Number — F830
Parameter Type —
Selection List
Factory Default —
0
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......