P9 ASD Installation and Operation Manual
Time-Based Alternation Process Hold Mode Response Time
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Process Hold
mode, this parameter sets the time that the system may operate within the
maximum or minimum
Virtual Linear Pump
zones before turning the ASD on
or off, respectively.
Direct Access Number — F438
Parameter Type —
Numerical
Factory Default —
7.5
Changeable During Run —
No
Minimum — 0.0
Maximum — 6553.5
Units — Seconds
Time-Based Alternation Direct Mode Response Time
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, while running in the
Direct
mode,
this parameter sets the time that the system may operate within the maximum or
minimum
Virtual Linear Pump
zones before turning the ASD on or off,
respectively.
Direct Access Number — F439
Parameter Type —
Numerical
Factory Default —
1000
Changeable During Run —
No
Minimum — 0
Maximum — 65535
Units — Seconds
Power Running Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting.
If
Setting
is selected, the value set at
is used as the
Power Running
Torque Limit 1
input.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
(Setting)
Direct Access Number — F440
Parameter Type —
Selection List
Factory Default —
Changeable During Run —
Yes
Power Running Torque Limit 1 Level
Program
Torque
Torque Limit Settings
This parameter provides a value for the
Power Running Torque Limit 1
setting if the
F441 setting
is selected at parameter
.
This value provides the positive torque upper-limit for the
1
motor.
Direct Access Number — F441
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 1
Program
Torque
Torque Limit Settings
This parameter determines the source of the
Regenerative Torque Limit
control signal.
If
Setting
is selected, the value set at
is used for this parameter.
Settings:
1 — V/I
2 — RR
3 — RX
4 —
(Setting)
Direct Access Number — F442
Parameter Type —
Selection List
Factory Default —
Setting
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......