P9 ASD Installation and Operation Manual
21
I/O and Control
The ASD can be controlled by several input types and combinations thereof, as well as operate within a
wide range of output frequency and voltage levels. This section discusses the ASD control methods and
supported I/O functions.
The
Terminal Board
supports discrete and analog I/O functions and is shown in
lists the names, functions, and settings (default settings of programmable terminals) of the input
and output terminals of the
Terminal Board
.
Note:
To use the input lines of the
Terminal Board
to provide
Run
commands, the
Command Mode
setting must be set to
Terminal Block
.
Typical Connection Diagram on pg. 26
shows the typical connection diagram for the ASD system.
Table 2. Terminal Board Terminal Names and Functions.
Terminal
Name
Input/Output
Function
(Default Setting If Programmable)
(see
Terminal Descriptions on pg. 22
)
Circuit Config.
ST
Discrete Input
Connect to CC
to activate
(Sink mode).
Standby
— Multifunctional programmable discrete input. Activation required
for normal ASD operation.
RES
Reset
— Multifunctional programmable discrete input. Resets a faulted ASD.
F
Forward
— Multifunctional programmable discrete input.
R
Reverse
— Multifunctional programmable discrete input.
S1
Preset Speed 1
— Multifunctional programmable discrete input.
S2
Preset Speed 2
— Multifunctional programmable discrete input.
S3
Preset Speed 3
— Multifunctional programmable discrete input.
S4
Preset Speed 4
— Multifunctional programmable discrete input.
Switched
Output
External Device 1
— Programmable contact (N.O.).
External Device 2
— Programmable contact (N.O.).
Fault relay (N.O.).
Fault relay (N.C.).
Fault relay (common).
Analog Input
Frequency Mode 1
—
Multifunction programmable analog input. (0.0 to 10
VDC input — 0 Hz to Maximum Frequency).
Multifunctional programmable analog input (-10 to +10 VDC input).
(select V or I
via
)
Unassigned
—
V
— Multifunctional programmable isolated analog voltage
input (0 to 10 VDC input).
Frequency Mode 2
(default
setting)
—
I
— Multifunctional
programmable isolated analog current input (4 [0] to 20 mADC input — 0 Hz
to Maximum Frequency).
Analog Output
Output Current —
Voltage output that is proportional to the output current of
the ASD or to the magnitude of the function assigned to this terminal.
Output Frequency —
Current or Voltage output that is proportional to the
output frequency of the ASD or to the magnitude of the function assigned to
this terminal. Select
Current
or
Voltage
at
DC Input
Externally-supplied 24 VDC backup control power (1.1 A min.). An alternative to the EOI
.
DC Output
24 VDC output (200 mA max.).
10.0 VDC/10 mA voltage source for an external potentiometer.
Pulsed Output
Frequency Pulse
— Multifunctional programmable output pulse train of a
frequency based on the output frequency of the ASD.
IICC
—
Return for the
V/I
input terminal (see
IICC
on
DO NOT
connect
to
Earth Gnd
.
CCA
—
Return for the
RR
,
RX
,
P24
, and the
PP
terminals.
CC
—
Return for the
AM
,
FM
,
+SU
, and the discrete input terminals.
V
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......