206
P9 ASD Installation and Operation Manual
MON2 Terminal Adjustment
Program
Terminal
Analog Output Terminals
This parameter is used to set the gain of the
MON2
output terminal and is used
in conjunction with the settings of
.
See
for additional information on this parameter.
Direct Access Number — F675
Parameter Type —
Numerical
Factory Default —
512
Changeable During Run —
Yes
Minimum — 1
Maximum — 1280
FP Terminal Assignment
Program
Terminal
Analog Output Terminals
This parameter sets the functionality of the
FP
output terminal to any one of the
user-selectable functions listed in
As the assigned function changes in magnitude or frequency, the pulse count of
the
FP
output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
This parameter is used in conjunction with
Direct Access Number — F676
Parameter Type —
Selection List
Factory Default —
Output Frequency
Changeable During Run —
Yes
FP Terminal Frequency
Program
Terminal
Analog Output Terminals
This parameter scales the
FP
output terminal by setting the pulses-per-second
output signal of the
FP
terminal.
See
for additional information on this parameter.
Direct Access Number — F677
Parameter Type —
Numerical
Factory Default —
3.84
Changeable During Run —
Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
FM Voltage/Current Output Switching
Program
Terminal
Analog Output Terminals
This parameter is used to select the type of output signal provided at the
FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See
for additional information on this parameter.
Settings:
0 — 0 – 10 V
1 — 0 – 20 mA
Direct Access Number — F681
Parameter Type —
Selection List
Factory Default —
0–10V
Changeable During Run —
No
FM Output Gradient Characteristic
Program
Terminal
Analog Output Terminals
This parameter sets the output response polarity of the
FM
output terminal. The
FM
output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See
for additional information on this parameter.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F682
Parameter Type —
Selection List
Factory Default —
Plus
Changeable During Run —
Yes
FP
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......