232
P9 ASD Installation and Operation Manual
My Function Time Data 4
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 4
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F931
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Time Data 5
Program
My Function
My Function Data
This parameter is used to set the response delay of the
My Function Time
Data 5
terminal.
The applied discrete input signal must be present at the input terminal of the
P9 ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number — F932
Parameter Type —
Numerical
Factory Default —
0.01
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Count Data 1
Program
My Function
My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output
COUNT1 (ON Timer)
.
COUNT1 (ON Timer)
outputs a 1 upon reaching the threshold setting of this
parameter.
Direct Access Number — F933
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 9999
Units — Pulses
My Function Count Data 2
Program
My Function
My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output
COUNT2 (ON Timer)
.
COUNT2 (ON Timer)
outputs a 1 upon reaching the threshold setting at this
parameter.
Direct Access Number — F934
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 9999
Units — Pulses
Input Function Target 1
Program
My Function
My Function Unit 4
This parameter plays a role in the setup of the
My Function
feature by
selecting the functionality of the programmable
Input Function Target 1
terminal.
This setting assigns the function of the programmable
Input Function Target 1
terminal to any one of the user-selectable functions listed in
, or
See
for additional information on this parameter.
Direct Access Number — F935
Parameter Type —
Selection List
Factory Default —
0 (Disabled)
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......