P9 ASD Installation and Operation Manual
165
Regenerative Braking Torque Limit 1 Level
Program
Torque
Torque Limit Settings
This parameter provides a value to be used as the
Regeneration Torque
Limit 1
if the
F443 setting
is selected at parameter
Set this parameter to
250%
to disable this function.
Direct Access Number — F443
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 249.9
Units — %
Power Running Torque Limit 2 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the
2
motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Set this parameter to
250%
to disable this function.
Direct Access Number — F444
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 2 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the
2
motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Set this parameter to
250%
to disable this function.
Direct Access Number — F445
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 3 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the
3
motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Set this parameter to
250%
to disable this function.
Direct Access Number — F446
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Regenerative Braking Torque Limit 3 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the negative torque upper-limit for the
3
motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Set this parameter to
250%
to disable this function.
Direct Access Number — F447
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Power Running Torque Limit 4 Level
Program
Torque
Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the
4
motor
profile when multiple motors are controlled by a single ASD or when a single
motor is to be controlled by multiple profiles.
Set this parameter to
250%
to disable this function.
Direct Access Number — F448
Parameter Type —
Numerical
Factory Default —
250.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0 (Disabled)
Units — %
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......