P9 ASD Installation and Operation Manual
163
Speed Limit (torque=0) Center Value
Program
Torque
Torque Speed Limiting
This parameter provides a value to be used as the
Speed Limit (torque=0)
Center Value Reference
setting if the F431 setting is selected at
Direct Access Number — F431
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Speed Limit (torque=0) Band
Program
Torque
Torque Speed Limiting
The system has the ability to limit the amount that the speed may vary as a
function of a changing load while operating in the
Torque Control
mode. This
parameter sets a plus-or-minus value (range) for the
Speed Limit Torque
Level
).
Direct Access Number — F432
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Time-Based Alternation Pump Number
Program
Virtual Linear Pump
Time-Based Alternation
During
Time-Based Alternation
operation, this parameter is used to assign an
identifying number to an ASD/pump combination.
The identifying number is used to assign the virtual priority Lead and Lag
assignments.
The maximum number is limited to the user-assigned number at parameter
Note:
This parameter is not associated with nor affected by the setting
of
Direct Access Number — F434
Parameter Type —
Selection List
Factory Default —
1
Changeable During Run —
Yes
Minimum — 1
Maximum —
Setting
Rotation in Specified Direction ONLY
Program
Torque
Torque Speed Limiting
This parameter
Enables/Disables
the
Forward Run
or
Reverse Run
mode.
If either direction is disabled, commands received for the disabled direction will
not be recognized.
If both directions are disabled, the received direction command will determine
the direction of the motor rotation.
Settings
0 — Disabled
1 — Enabled
Direct Access Number — F435
Parameter Type —
Selection List
Factory Default —
Disabled
Changeable During Run —
No
Time-Based Alternation Total Number of ASDs
Program
Virtual Linear Pump
Time-Based Alternation
This parameter lists the number of ASDs registered within the system.
This parameter setting is used as the
Maximum
setting for parameter
.
Direct Access Number — F437
Parameter Type —
Numerical
Factory Default —
2
Changeable During Run —
Yes
Minimum — 2
Maximum — 32
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......