P9 ASD Installation and Operation Manual
97
Input Terminal 4 (RES) Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
RES
terminal input by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F143
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 5 – 12 Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
5 – 12
terminal inputs by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F144
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 13 – 20 Response Time
Program
Terminal
Input Terminal Delays
This parameter delays the response of the ASD to any change in the
13 – 20
terminal inputs by the programmed value (see waveforms at
).
The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.
Direct Access Number — F145
Parameter Type —
Numerical
Factory Default —
8.0
Changeable During Run —
No
Minimum — 2.0
Maximum — 200.0
Units — mS
Input Terminal 17 (B12) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
B12
discrete input
terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the functionality of the programmable
B12
terminal to any
one of the user-selectable functions listed in
.
See the
My Function
Instruction Manual
(P/N E6581335) for additional
information on the function of this terminal.
Direct Access Number — F164
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Input Terminal 18 (B13) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the
B13
discrete input
terminal.
In addition, this input terminal must be specified as
Normally Open
or
Normally Closed
.
This setting assigns the function of the programmable
B13
terminal to any one
of the user-selectable functions listed in
.
See the
My Function
Instruction Manual
(P/N E6581335) for additional
information on the function of this terminal.
Direct Access Number — F165
Parameter Type —
Selection List
Factory Default —
Unassigned
Changeable During Run —
No
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......