P9 ASD Installation and Operation Manual
211
Panel Stop Pattern
Program
Special
Operation Panel Parameters
While operating in the
Hand
mode, this
parameter determines the method used
to stop the motor when the stop command is issued via the EOI.
The
Deceleration Stop
selection enables the
Dynamic Braking
system that is
set up at
or the
DC Injection Braking
system that is set up at
,
,
and
The
Coast Stop
setting allows the motor to stop at the rate allowed by the
inertia of the load.
Settings:
0 — Deceleration Stop
1 — Coast Stop
Note:
The
Stop Pattern
setting has no effect on the
Emergency Off
settings of
. This parameter may also be accessed by
pressing the
ESC
key from the
Frequency Command
screen.
Direct Access Number — F721
Parameter Type —
Selection List
Factory Default —
Deceleration Stop
Changeable During Run —
Yes
Panel Torque Command
Program
Special
Operation Panel Parameters
This function is not used with the P9 ASD.
The
Torque Command
Direct Access Number — F725
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Panel Tension Torque Bias
Program
Special
Operation Panel Parameters
This function is not used with the P9 ASD.
The
Tension Torque Bias
Direct Access Number — F727
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Panel Load Sharing Gain
Program
Special
Operation Panel Parameters
This function is not used with the P9 ASD.
The
Load Sharing Gain
selection is performed at
Direct Access Number — F728
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.00
Units — %
Panel Override Multiplication Gain
Program
Special
Operation Panel Parameters
This parameter provides a value to be used in the event that
Setting
(
) is
selected for the
Frequency Override Multiplying Input
(
).
Direct Access Number — F729
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — -100.00
Maximum — 100.00
Units — %
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......